Features:
>> One input: Pt100 (-200 ~ +600 ℃) (scope optional)
Also can choose Pt1000/Cu50/Pt10/Cu100
>> Two output signal: 4-20mA / 0-5V/0-10V standard signal
>> Accuracy: 0.2 (FSR%)
>> Containing linear and long-term compensation
>> Power supply: 5V/12V/15V/24VDC
>> Isolation voltage: 2500VDC (1mA, 60S)
>> Four isolation: input/output 1/output 2/power supply
>> Installation: DIN35 rail
>> Industrial temperature range: - 40 ~ + 85 deg.C
>> Size:106.7x79.0x25.0mm
Product description:
The product is isolated Pt100/PT1000/PT10/Cu50/Cu100 temperature sensor transmitter, in industry mainly used for measuring the temperature of -200 ~ +600deg.C. The transmitter has linear and long-term compensation, the factory in accordance with national standard Pt100 indexing table calibration, fully meets 0.2accuracy. Input, output 1, output 2 and auxiliary power supply is completely isolated (four isolation), can withstand 2500VDC isolation voltage. Products using international standards for rail mounting DIN35, small size, high precision, stable performance, cost-effective, can be widely used in petroleum, chemical, power, instrumentation and industrial control industries.
Samples:
signal Input: Pt100,temperature range:0~100℃; signal output 1:4-20mA; signal output 2:4-20mA , power:24VDC
Part No.: DIN12-Z1-T2-P1-A4
signal Input: Pt1000,temperature range:0~200℃; signal output:0-10V; signal output:0-10V , power:12VDC
Part No.: DIN12-Z5-T4-P2-V2
General parameters:
>> Accuracy ------- 0.2% (relative to temperature)
>> Input ------- three-wire, four-wire or two-wire RTD signal, you can choose Pt100, Pt1000, Pt10, Cu50, Cu100 thermal
resistance.(Need to select a temperature range and a output signal)
>> Output ------- standard voltage or current signal. Can also be user-defined
>> Response time ------- ≤ 100mS
>> Auxiliary power ------- DC5V, 9V, 12V, 15V, 24V
>> Power ------- <2W
>> Temperature drift ------- 50ppm / ℃ (typical)
>> Load capacity ------- voltage output: ≥ 2 kΩ
>> Current output: ≤ 450Ω
>> Isolation ------- signal input / output 1 / output 2/ auxiliary power isolation
>> Isolation voltage ------- 2500VDC, 1 minute, leakage current (1mA)
>> Impact resistance voltage ------- 3KV, 1.2/50us (peak value)
>> Operating Temperature -------- -40 to +85 ° C
>> Storage Temperature -------- -45 ~ +80 ℃
>> Operating Humidity ------- 10 ~ 90% (no condensation)
>> Storage Humidity ------- 10 ~ 95% (no condensation)
Warranty:
Two years (but violate operating rules and requirements to create damage, clients need pay maintenance costs)